A 100 ft 12/3 cord loses about 5% at 15 A, and the tool at the end pays for it. Work the run length out before the order, not after.

Extension Cord Voltage Drop: How Long?
A cord that is too long for its gauge does not fail dramatically. It works, badly. The saw bogs down in thick stock, the compressor trips its breaker on start, the drill smells hot after twenty minutes, and the customer concludes the tool is worn out. Nothing in that list points at the cord, which is why the complaint usually arrives as a return rather than a question.

A long cord is a resistor with a plug on each end

Every conductor has resistance, published in ohms per thousand feet, and a run uses that conductor twice: out to the load and back. So the resistance the load sees is the table figure, multiplied by the length in feet and divided by a thousand, then doubled. The voltage lost is that figure times the current, and the percentage is that loss divided by the supply voltage.
Put numbers on it. Uncoated stranded copper at 75 degrees C measures 1.98 ohms per thousand feet at 12 AWG. A 100 ft run therefore gives a loop resistance of about 0.40 ohms. At 15 A the cord loses 5.9 V, which on a 120 V supply is just under 5 percent. The tool is being fed 114 V, not 120, and the cord itself is dissipating about 89 W as heat along its length.

The 3 percent figure is a recommendation, not a rule

Almost every voltage drop article quotes 3 percent for a branch circuit and 5 percent for the feeder plus branch combined. Those numbers come from informational notes in the code, not from an enforceable requirement, and a distributor should say so plainly rather than presenting them as law. Some articles do set hard limits for particular equipment, and project specifications and equipment manufacturers frequently set tighter ones. If a customer asks whether 4 percent is illegal, the honest answer is no, but it may still be the reason their compressor will not start.
Cord, 100 ft at 120 V
Ohms per 1,000 ft (stranded, 75 C)
Loop resistance
Drop at 12 A
Amps that stay within 3%
14/3
3.14
0.63 ohms
7.5 V (6.3%)
5.7 A
12/3
1.98
0.40 ohms
4.8 V (4.0%)
9.1 A
10/3
1.24
0.25 ohms
3.0 V (2.5%)
14.5 A
Read the last column before you read the price column. A 100 ft 12/3 cord only holds 3 percent up to about 9 A. Most buyers assume 12 AWG means 15 or 20 A, and electrically the conductor will carry it, but the volts arriving at the far end will not be what the tool was designed around. That gap between ampacity and usable length is the whole subject.

How far can you actually run

Turn the calculation around and it becomes a purchasing tool. Fix the load at 12 A, fix the supply at 120 V, and solve for the length that keeps the drop at 3 and 5 percent.
Cord
Maximum length at 12 A, 3%
Maximum length at 12 A, 5%
14/3
48 ft
80 ft
12/3
76 ft
126 ft
10/3
121 ft
202 ft
Two patterns are worth memorising. Every two gauge steps roughly halves the resistance, which is why 10 AWG buys about 60 percent more distance than 12 AWG rather than a small improvement. And the supply voltage matters as much as the gauge: the same tool drawing the same power at 230 V pulls half the current, so the percentage drop falls to about a quarter. A run that is marginal on a 120 V site is comfortable on a 230 V one, which is why European and North American advice on cord length does not transfer.

What the load does with the missing volts

Not every load reacts the same way, and that difference decides how bad the complaint will be. A resistive load such as a heater simply produces less heat; it is inefficient but stable. A switch-mode power supply on a wide input range usually copes without complaint. An induction motor is the problem case: at reduced voltage it produces less torque, so it draws more current to do the same work, which raises the drop further and heats both the motor and the cord. That is the mechanism behind a saw that bogs in thick stock and a compressor that trips on start rather than while running.
Two conditions make it worse. A cord left coiled on a reel cannot shed the heat it generates, because the inner turns are wrapped in their own warmth, so a run that is merely marginal when laid out becomes hot when wound up. And resistance rises with conductor temperature, so a cord already working hard drops slightly more than the table figure suggests. The table is a starting point, not a guarantee.

Specifying the cord, not just the length

Four decisions carry the specification. The gauge, from the load and the run rather than from habit. The jacket, from the environment, since an outdoor site and an indoor bench do not need the same compound. The ends, because moulded connectors survive job sites better than field-fitted ones. And the marking and packaging the market requires. Our 100 ft 12/3 SJTW cord is built for exactly this duty: 12/3 AWG copper, an SJTW jacket rated for outdoor use, a lighted end connector and moulded terminations, at 30.48 m per cord, with OEM length, plug configuration and private-label packaging available.

Next step

Send us the tool or appliance, its current draw, the supply voltage and the distance you need to cover, and we will tell you which gauge holds the drop where you want it and quote the cord against it. OEM lengths, jacket colours, plug configurations and private-label packaging are available for volume programmes. Reach the team at /contact-us/ or message us on WhatsApp for a faster answer.